Page Title: Parallel Plant Operation
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books

   

 

Back
Plant Equipment
Up
Construction Electrician Intermediate - Electricity handbook for electricians
Next
Isolated Bus Operation

Parallel Plant Operation If the load of a single generator becomes so large that its rating is exceeded, you should add another generator in parallel to increase the power available for the generating station. Before two ac generators can be paralleled,  the  following  conditions  have  to  be fulfilled: 1. Their terminal voltages have to be equal. 2. Their frequencies have to be equal. 3. Their voltages have to be in phase. When two generators are operating so that the requirements  are  satisfied,  they  are  said  to  be  in synchronism.  The  operation  of  getting  the  machines into synchronism is called synchronizing. Generating plants may be operated in parallel on an isolated bus (two or more generators supplying camp or base load) or on an infinite bus (one or more generators paralleled to a utility grid). One  of  the  primary  considerations  in  paralleling generator sets is achieving the proper division of load. That can be accomplished by providing the governor of the generator with speed droop. That would result in a  regulation  of  the  system.  The  relationship  of REGULATION  to  LOAD  DIVISION  is  best explained by referring to a speed versus load curve of the governor. For simplicity,. we will refer to the normal speed as 100 percent speed and full load as 100 percent load. In the controlled system, we will be concerned with two types of governor operations: isochronous and speed droop. The operation of the isochronous governor (0 percent speed droop) can be explained by comparing speed  versus  load.  as  shown  in  figure  3-3.  If  the governor were set to maintain the speed represented by line A and connected to an increasing isolated load, the speed  would  remain  constant.  The  isochronous governor will maintain the desired output frequency, regardless of load changes if the capacity of the engine is not exceeded. The speed-droop governor (100 percent speed droop) has a similar set of curves. but they are slanted. as shown in figure 3-4. If a speed-droop governor were connected to an increasing isolated load, the speed would drop (line A. fig. 3-4) until the maximum engine capacity is reached. Now let’s imagine that we connect the speed- droop governor (slave machine) to a utility bus so large that our engine cannot change the bus frequency (an Figure 3-3.—Isochronous governor curve. Figure 3-4.—Speed-droop governor curve. infinite bus). Remember that the speed of the engine is no longer determined by the speed setting but by the frequency of the infinite bus. In this case, if we should change the speed setting, we would cause a change in load, not in speed. To parallel the generator set, we are required to have a speed setting on line A (fig. 3-4). at which the no-load speed is equal to the bus frequency. Once the set is paralleled. if we increase the speed setting to line B. we do not change the speed. but we pick up approximately a half-load. Another increase in speed setting to line C will fully, load the engine. If the generator set is fully loaded and the main breaker is 3-8