| |
Back Parallel Plant Operation | Up Construction Electrician Intermediate - Electricity handbook for electricians | Next Basic Operating Precautions |
opened, the no-load speed would be 4 percent above
synchronous speed. This governor would be defined as
having 4 percent speed droop.
Paralleling an isochronous governor to an infinite
bus would be impractical because any difference in
speed setting would cause the generator load to change
constantly. A speed setting slightly higher than the bus
frequency would cause the engine to go to full-load
position. Similarly, if the speed setting were slightly
below synchronous speed, the engine would go to no-
load position.
Setting speed droop on hydraulic governors is
accomplished by adjusting the speed-droop knob
located on the governor body. Setting the knob to
position No. 5 does not mean 5 percent droop. Each of
the settings on the knob represents a percentage of the
total governor droop. If the governor has a maximum
of 4 percent droop. the No. 5 position would be 50
percent of 4 percent droop. Setting speed droops on
solid-state electronic governors is accomplished by
placing the UNIT-PARALLEL switch in the
PARALLEL position. The governor speed droop is
factory set, and no further adjustments are necessary.
ISOLATED BUS OPERATION.In
the
following discussion, assume that one generator, called
the master machine, is operating and that a second
generator, called the slave machine, is being
synchronized to the master machine. Governor con-
trols on the master ernogenerator should be set to the
ISOCHRONOUS or UNIT position. The governor
setting on the slave generator must be set to the
PARALLEL position.
NOTE: The hydraulic governor droop setting is an
approximate value. Setting the knob to position No. 5 will
allow you to parallel and load the generator set. Minor
adjustments may be necessary to prevent load swings
after the unit is operational.
When you are paralleling in the droop mode with
other generator sets, the governor of only one set may
be in the isochronous position; all others are in the
droop position. The isochronous set (usually the
largest capacity set) controls system frequency and
immediately responds to system load changes. The
droop generator sets carry only the load placed on them
by the setting of their individual speed controls. Both
voltage regulators should be set for parallel and
automatic operation.
The slave machine is brought up to the desired
frequency by operating the governor controls. It is
preferable to have the frequency of the slave machine
slightly higher than that of the master machine to
assure that the slave machine will assume a small
amount of load when the main circuit breaker is closed.
Adjust the voltage controls on the slave machine until
the voltage is identical to that of the master machine.
Thus two of the requirements for synchronizing have
been met: frequencies are equal and terminal voltages
are equal.
There are several methods to check generator
phase sequence. Some generator sets are equipped
with phase sequence indicator lights and a selector
switch labeled GEN and BUS. Set the PHASE
SEQUENCE SELECTOR SWITCH in the BUS
position, and the 1-2-3 phase sequence indicating
light should light. (The same light must light in either
GEN or BUS position.) If 3-2-1 phase sequence is
indicated, the slave machine has to be shut down, the
load cables isolated, and two of the load cables
interchanged at their connection to the load terminals.
Another method to verify correct phase sequence
is by using the synchronizing lights. When the
synchronizing switch is turned on, the synchronizing
lights will start blinking. If the synchronizing lights
blink on simultaneously and off simultaneously, the
voltage sequences of the two machines are in phase.
The frequency at which the synchronizing lights blink
on and off together indicates the different frequency
output between the two machines. Raise or lower the
speed of the slave machine until the lights blink on
together and offtogether at the slowest possible rate. If
the synchronizing lights are alternately blinking (one
on while the other is off), the voltage sequence of the
two machines is not in phase. Correct this condition by
interchanging any two of the three load cables
connected to the slave machine.
Some of the portable generators being placed in
the NMCB Table of Allowances (TOA) are equipped
with a permissive paralleling relay. This relay, wired
into the main breaker control circuit, prevents the
operator from paralleling the generator until all three
conditions have been met.
Now that all three paralleling requirements have
been met, the slave machine can be paralleled and
loaded.
If a synchroscope is used, adjust the frequency of
the slave machine until the synchroscope pointer
rotates clockwise slowly through the ZERO position
(twelve oclock). Close the main circuit breaker just
before the pointer passes through the ZERO position.
To parallel using synchronizing lights, wait until the
3-9
|