ARMY TM 9-6115-642-24AIR FORCE TO 35C2-3-455-12MARINE CORPS TM 09247A/09248A-24/22-23.31. In-LineFuseInstallation.a.b.c.d.e.f .g.h.i .NOTEThe following procedure applies to generator sets under contract number DAAK01-88-D-D080Shut down generator set.Open left side engine access door and disconnect negative battery cable.Remove malfunction indicator panel screws (9, FIGURE 2-11), washers (10), and nuts (11). Laymalfunction indicator panel to the side.Cut black wire on load side of GROUND FAULT CIRCUIT INTERRUPTER (8).Strip wires on in-line fuse holder (2, FIGURE 2-10.1) and install butt splices (3) at each end. Connectends of black wire to in-line fuse holder butt splices (3).Install fuse (1) in fuse holder (2).Secure excess wire to wiring harness using tie wrap.Install malfunction indicator panel (12, FIGURE 2-11), screws (9), washers (10), and nuts (11).Reconnect negative battery cable and close left side engine access doorNOTEWhen replacing GROUND FAULT CIRCUIT INTERRUPTER, use new GROUNDFAULT CIRCUIT INTERRUPTER with integral circuit breaker. Refer to TM 9-6115-641-24P for new part number.Figure 2-10.1. In-Line Fuse Installation2-50 Change 4