TM 9-6150-226-134-17 CIRCUIT BREAKER ASSEMBLY AND BUS BAR. (cont)c.d.e.f.9.3. INSTALL BUS BAR.NOTEWhen removing ground busbar, disconnect and removeground strap connectingbus bar to enclosure.Tag and disconnect wiring (8)from bus bar terminals (9).Remove nut (10) securingbus bar (9) to feeder/distri-bution center. Remove bus bar.Tag and disconnect wiring (11 )from three phase bus bars (12).Remove screws (13) securingbus bars. Remove bus bars.Tag and disconnect wiring (14)from ground (15) andneutral (16) bus bars.Remove screws (17), nuts (18)and washers (19) securing busbars. Remove bus bars.Remove screw (20), nut (18), andwasher (19) securing ground strap.a.b.c.NOTEIf you have PDISE equipment, follow instructionsin paragraph 3c, d, e and f.Install bus bar (9) and securewith nut (10).Solder dip or solder gun wire ends,not to exceed .025 inches, using KesterSolder MIL Spec No. QQ-S-571(Sn 60 Pb 40).Refer to tags and connectwiring (8) to bus barterminals (9). Remove tagsand torque terminals inaccordance with table G-1.4-50Change 1