CONDUCTOR (GEC) The
main purpose of the grounding electrode conductor (GEC) is to connect the
electrical system to earth ground. The GEC actually provides three grounding
paths to the grounding electrode system. They are as follows:
1. The grounded conductor path
2. The equipment grounding path
3. The bonding path.
In
grounded systems, the GEC connects to the neutral bar in the service equipment
enclosure. In ungrounded systems, the GEC connects to the grounding terminal
bar. It grounds the following items to the grounding electrode system:
1. The grounded conductor, if present
2. The equipment grounding conductor, if
present
3. The metal of conduits, if present
4. The metal of enclosures, if present
5. The bonding jumpers bonding together
metal enclosures and conduits
6. The metal enclosure of the service
equipment.
4.7.1 SIZING THE GROUNDING ELECTRODE CONDUCTOR
NEC
Section 250-94 requires the grounding electrode conductor to be sized by the
circular mils rating of the largest service entrance conductor or conductors
and selected from NEC Table 250-94 based on these values.
For
example, the size of the service entrance conductors from a delta, three-phase,
four-wire midpoint tap is #250 kcmil, THWN copper for phases A and C, #2/0 for
phase B, and #1/0 for the neutral. What size copper GEC is required to ground
this system to a metal water pipe?
Step
1:Finding the largest phase-NEC 250-94
#250 kcmil is the largest phase
Step
2:Finding the size GEC-NEC Table 250-94
#250 kcmil requires #2 cu
Answer: The size of grounding electrode
conductor (GEC) is at least #2 copper.
Note:
NEC Table 250-94 is used to size the grounding electrode conductor for both
grounded and ungrounded systems. The table is used where the grounding
electrode conductor is connected to a metal water pipe or the metal frame of
building steel.
4.7.2 EXCEPTIONS TO NEC 250-94
There
is an exception to the main rule. It has three parts and pertains to specific
types of grounding electrodes. The exception applies to grounded and ungrounded
systems.
Exception
(a) applies to made electrodes only, such as rod, pipe, or plate electrodes.
The grounding electrode conductor is not required to be larger than #6 copper
or #4 aluminum.
Exception
(b) to NEC Section 250-94 requires at least a #4 copper conductor to be used as
a grounding electrode conductor to ground the electrical system to a
concrete-encased electrode.
Exception
(c) requires at least a #2 copper conductor to be used as a grounding electrode
conductor to ground the electrical system to a ground ring. [See NEC Section
250-81(d)]
4.8 MAIN BONDING JUMPER
The
primary function of the main bonding jumper is to connect the grounded circuit
conductors and the equipment grounding conductors at the service equipment. The
main bonding jumper serves as the main link between the system grounded
conductors and the grounding electrode system where metal equipment enclosures
and raceways are utilized to enclose conductors and components. If the main
bonding jumper is left out, there is not a complete circuit for fault current
and is an invitation to a dangerous situation.
The
main bonding jumper shall connect together the following items:
1. Grounded conductors and grounded
terminal
2. Equipment grounding conductors and
grounding terminal
3. All metal enclosures enclosing
conductors and components.
If
supplied, the manufacturers main bonding jumper is the preferred conductor to
be used as the main bonding jumper. NEC Section 250-79(a) requires the main
bonding jumper to be a (1) wire, (2) screw, (3) busbar, or (4) a similar
suitable conductor.
NEC
Section 250-79(d) requires the main bonding jumper to be at least the same size
as the grounding electrode conductor where the circular mils rating of the
service entrance conductors does not exceed 1100 kcmil for copper or 1750 kcmil
for aluminum.
For
example: What size main bonding jumper is required to ground the metal
enclosure of the service equipment to the grounding terminal bar where the
service entrance is made up of one #250 kcmil, THWN copper conductor per phase?
Step
1: Step 2: Answer:
Finding
the largest phase-NEC 250-79(d) #250 kcmil is the largest phase Finding the
bonding jumper-Table 250-94 #250 kcmil requires #2 copper The size of the main
bonding jumper (GEC) is at least #2 copper.
Where
the kcmil rating of the service entrance conductors exceeds 1100 kcmil for
copper or 1750 for aluminum, the bonding jumper shall be at least 121/210 of
the largest kcmil rating of any one phase.
For
example: What size main copper bonding jumper is required for a service
entrance with a makeup of 2400 kcmil copper conductors per phase?
Step
1:Finding the largest phase-NEC 250-79(d)
2400 kcmil x 0.125 = 300 kcmil
Step
2:Finding the main bonding jumper-NEC
Table 250-94; Table 8, Ch. 9 requires 300 kcmil
Answer: The main bonding jumper is required
to be at least 300 kcmil copper.
Note:
In this case the main bonding jumper is greater in size than the grounding
electrode conductor, which is only required to be #3/0 copper per NEC Table
250-94 based upon the 2400 kcmil copper conductors.
|