BATTERY ROOM There
are no special requirements for the type of fixtures or other electrical
equipment used in the battery room, with proper ventilation. (See NEC 480-8 and
Figure 6-4)
Figure
6-4. With proper ventilation there are no special requirements for wiring and
equipment installed in battery rooms per NEC 480-8.
6.5.6
PERSONAL PROTECTIVE EQUIPMENT
Personal
protective equipment (PPE) capable of protecting employees from acid splashes
shall be used by those working on or servicing batteries. The minimum
acceptable PPE shall include acidresistant gloves, aprons, and chemical-splash
goggles. A full-face shield may also be used; it shall not, however, be worn in
place of goggles.
The
design and use of PPE for wear when servicing batteries shall comply with the
requirements of 29 CFR 1910.132,.133, and. 136. See NESC, Rule 146 and IEEE
450, Section 4.2.2. For information on safety showers and eyewash stations, see