Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  

 
You can see from the formula above that the CURRENT (I) varies inversely to the RESISTANCE (R). To maintain the required current flow disconnecting the service conductors from the supply source. It may consist of a single manually operated switch or a circuit breaker. The NEC sets a minimum size for entrance switches at 60 A for the fuse type and 50A for the circuit breaker type. A CIRCUIT BREAKER is a protective device that automatically opens the circuit, rather than burning out like a fuse, when the amperage exceeds that rated for the circuit breaker. The NEC recommends a minimum size of 100-A service for individual residences. However, when not more than two two-wire branch circuits are installed, a 30-A entrance switch may be used.

Panelboard

A PANELBOARD (fig. 9-10) is defined by the NEC as a single panel, or a group of panel units designated for assembly in the form of a single panel, including buses. It comes with or without switches and/or automatic overcurrent protective devices for the control of light, heat, or power circuits of small individual as well as aggregate capacity; it is designed to be placed in a cabinet or a cutout box and placed in or against a wall or partition and is only accessible from the front.

A BREAKER PANEL uses a thermal unit built into the switch with the breaker being preset at the factory to open automatically at a predetermined  

Figure 9-11.-Lighting panel.

ampere setting. It maybe reset to the ON position after a short cooling-off period.

LIGHTING PANELS (fig. 9-11) are normally equipped with 15-A single-pole automatic circuit breakers, while the power panels may have one-, two-, or three-pole automatic circuit breakers with a capacity to handle the designated load. In most buildings, the entrance switch and panelboards can be mounted close to each other; however, they must be placed where service and maintenance can be easily performed. They should not block any passage that is supposed to be open, and they should not be in a place where exposure to corrosive fumes and dampness is imminent. Panelboards should be located as near as possible to the center of the electrical load. Conductors

ELECTRICAL CONDUCTORS generally consist of drawn copper or aluminum formed into wire. They provide paths for the flow of electrical current. Conductors are usually covered with insulating materials (fig. 9-12) to minimize the 

Figure 9-12.-Types of single insulated conductors. 

chances for short circuits and to protect personnel. Atmospheric conditions, voltage requirements, and environmental and operating temperatures are factors to consider in selecting the type of insulating material for a particular job.







Western Governors University
 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business