CONDENSERS The compressor discharge line terminates at the
refrigerant condenser. In shipboard installations, these condensers are
usually of the multipass shell-and-tube type, with water circulating
through the tubes. The tubes are expanded into grooved holes in the tube
sheet to make a tight joint between the shell and the circulating water.
Refrigerant vapor is admitted to the shell and condenses on the outer
surfaces of the tubes.
Any air or noncondensable gases that may accidentally
enter the refrigeration system will be drawn through the piping and
eventually discharged into the condenser with the refrigerant. The air
or noncondensable gases accumulated in the condenser are lighter than
the refrigerant gas. They will rise to the top of the condenser when the
plant is shut down. A purge valve, for purging the refrigeration system
(when necessary), is installed at the top of the condenser or at a high
point in the compressor discharge line.
Cleaning Condenser Tubes
To clean the condenser tubes properly, first drain the
cooling water from the condenser. Then disconnect the water connections
and remove the condenser heads. Be careful not to damage the gaskets
between the tube sheet and the waterside of the condenser heads. Inspect
tubes as often as practical and clean them as necessary, using an
approved method. Use rubber plugs and an air lance or a water lance to
remove foreign deposits. You must keep the tube surfaces clear of
particles of foreign matter. However, you must not destroy the thin
protective coating on the inner surfaces of the tubes. If the tubes
become badly corroded, replace them. Replacement avoids the possibility
of losing the charge and admitting salt water to the system.
Cleaning Air-Cooled Condensers
Although the large plants are equipped with
water-cooled condensers, auxiliary units are commonly provided with
air-cooled condensers. The use of air-cooled condensers eliminates the
necessity for circulating water pumps and piping.
Keep the exterior surface of the tubes and the fins on
an air-cooled condenser free of dirt or any matter that might obstruct
heat flow and air circulation. The finned surface should be brushed
clean with a stiff bristle brush as often as necessary. Low-pressure air
is very useful in removing dirt in hard-to-reach places on condensers.
When installations are exposed to salt spray and rain through open doors
or hatches, you should take steps to minimize corrosion of the exterior
surfaces.
Testing For Leaks
To prevent serious loss of refrigerant through leaky
condenser tubes, test the condenser for leakage by following the PMS.
To test for leaky condenser tubes, drain the waterside
of the condenser. Then insert the exploring tube of the leak detector
through one of the drain plug openings. If this test indicates that
Freon gas is present, you can find the exact location of the leak by
following these steps:
1. Remove the condenser heads.
2. Clean and dry the tube sheets and the ends of the
tubes.
3. Check both ends of each tube with a leak detector.
Mark any tubes that show leakage. If you cannot determine that a tube is
leaking internally or around the tube sheet joint, plug the suspected
tube and again check around the tube sheet joint. Mark the adjacent
tube, if necessary, to isolate the suspected area.
4. To locate or isolate very small leaks in the
condenser tubes, hold the exploring tube at one end of the condenser
tube for about 10 seconds to draw fresh air through the tube. Repeat
this procedure with all the tubes in the condenser. Allow the condenser
tubes to remain plugged for 4 to 6 hours; then, remove the plugs one at
a time and check each tube for leakage. If a leaky tube is detected,
replace the plug immediately to reduce the amount of refrigerant
escaping. Make appropriate repairs or mark and plug all leaky tubes for
later repairs.
Plugging or Retubing Condensers
The general procedures for plugging or retubing
condensers can be found in Naval Ship's Technical Manual (NSTM),
Chapter 254, Condensers, Heat Exchangers, and Air Ejectors. When
plugging or retubing a specific condenser, follow the procedures in the
manufacturers technical manual.
|