Custom Search
|
|
SIZING OF SERVICE-ENTRANCE CONDUCTORS The most important point to remember when you are determining the size of service-entrance conductors is to ensure they are large enough to carry the load. A conductor that is too small may become overheated and create a fire hazard. On the other hand, sizing the conductors far too large to supply the load can be expensive and unnecessary. The NECR (Section 230-42(b)) has established the minimum size for service-entrance conductors as the following: 1. 100-ampere for a three-wire service to a single-family dwelling with six or more two-wire branch circuits. 2. 100-ampere for a three-wire service to a single-family dwelling when the total load has been determined to be 10 kVA or more. 3. 60-ampere service for other loads. Determine the size of the service-entrance conductors in the following example. Given: 1,600-sq-ft dwelling with 120-/240-V, single-phase service Two small appliance loads and one laundry load Special appliance loads 12-kVA range 6.0-kVA dryer 15-kVA central heater 9.0-kVA air conditioner 4.8-kVA water heater 1.2-kVA dishwasher 0.8-kVA disposal 1.6-kVA attic fan 0.4-kVA vent fan Solution: General lighting and receptacle loads 1,600 sq ft 3 VA = 4,800 VA Small appliance loads
The demand factor (table 3-2) for general lighting and small appliance loads is as follows: First 3,000 VA 100 percent = 3,000 VA Remaining 6,300 VA 35 percent = 2,205 VA Total demand load = 5,205 VA 12-kVA range The demand factor (table 3-4) for a 12-kVA range is 8 kVA. Total demand load = 8,000 VA 6.0-kVA dryer The demand factor (table 3-3) for one 6-kVA dryer is 100 percent. Total demand load = 6,000 VA Heating and air conditioning The smallest load (air conditioning) can be disregarded. The demand factor for heating load is 100 percent. Total demand load = 15,000 VA Fixed appliances The demand factor for four or more fixed appliances is 75 percent.
8,800 VA 75 percent of demand factor = total demand load of 6,600 VA |
||