|
|
Deluge and Pre-Action Valves To test deluge and pre-action valves, perform the 2-inch drain test quarterly by opening the 2-inch drain valve fully and recording pressure at lowest point. Close the 2-inch drain valve and record pressure at the stabilization point. Notice whether pressure returns quickly or slowly. Maintain a continuous record of drain tests. If the recorded pressure when the valve is wide open is similar to previous recordings and pressure returns quickly, it is normal. If the recorded pressure when the valve is wide open is significantly lower or pressure is slow to return when the valve is closed, there may be an obstruction in the waterway. Check for partially closed valves to the sprinkler system. Check the water pressure and the local water-flow alarm through the bypass connection. Some deluge systems have both open and closed sprinklers. Make sure heat-responsive devices are provided in areas with both open and closed sprinklers and are in service. Fusing of a sprinkler will not operate a deluge valve. Where conditions permit, trip-test each deluge valve every 3 years by flowing water through the heads/ nozzles. To conduct a deluge valve dry trip-test, do the following: 1. Close the main control valve. 2. Apply an electric heat lamp to at least one heat-actuating device in each circuit, testing one circuit at a time. Note the time required to trip the valve. Where flammable vapors may be present, use a hot cloth or hot water in place of the electric test set. 3. Reset the deluge valve and trip, using the manual release. 4. Where fixed temperature releases are involved, wait 15 minutes and trip by removing a fusible element from the tubing or a heatresponsive device. 5. When tests are complete, reset valves and open the main control valves. Because there are so many designs of heatresponsive devices, test procedures for each cannot be included here. See the individual manufacturer's information for detailed testing procedure. During routine inspections, check for painted or corroded contacts, plugged vents, or painted domes. Clean or replace affected devices. Cathodic Protection Equipment Inspect cathodic protection equipment as follows: 1. While equipment is operating, note and record current flow shown by meters. If there is no current, check for blown fuses, electrodes touching the tank, ground-wire connection to tank, or electrodes not immersed in the water. If equipment operates at voltages or amperages over those listed on the nameplate, the rectifier may be damaged. Check polarity and direction of current flow. (If connections to rectifier are reversed, rapid damage to the tank occurs.) 2. Check condition of electrodes that deteriorate because of action of current passing from electrodes to water. Replace worn electrodes. (Watch for diminishing current flow on the ammeter; this is a sign that the electrodes may be failing.) 3. Protect electrodes from ice. If ice formation is a serious problem, turn off current and remove and store the electrodes during the freezing season. Tank protection will continue for about 3 weeks after the unit is out of operation. Reinstall the electrodes at the end of the freezing season. |
Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing |