|
|
Duct and Outlet Adjustments You should use the same procedure for measuring total air volume to set the main splitter dampers on systems containing branch ducts. When main ducts, zone ducts, and branches are set for design air, the tests necessary for adjusting individual outlets can begin. When available, always follow the manufacturer's recommended procedure. The final balancing procedure involves the adjustment of individual outlets to correspond with the manufacturer's design flow and system specifications. Begin with the last outlet on the branch farthest from the fan discharge and measure the velocity (or cfm). You can use either a velometer with the diffuser probe or an anemometer. If the cfm is below design, leave the damper open and proceed to the next outlet. If the cfm is greater than design, close the damper to obtain the desired results. In the same branch go to the next closest outlet, repeat the procedure, then continue the process with each outlet until you reach the main duct. If applicable, you should complete the same procedure on the remaining branch ducts. Finally, total cfm of all outlets should agree with total cfm of all branches, and this grand total should agree with the air volume for the fan or fans. These figures should be within 3 to 7 percent of design conditions. You should check fan outputs and motor amperages to ensure that the motor is not in an overloaded condition. At this point, fan speed and horsepower, fan total air by velocity measurement, and total air by outlet volume measurements have been established for the specific operating condition of the system during the procedure. The system should be balanced for those conditions. VENTILATION SYSTEMS Normally air contains about 21 percent oxygen. A ventilation system serving human beings requires that a certain oxygen content be contained in the air to maintain life and to ensure comfort. If a room is tightly sealed, any human in that room would slowly consume the oxygen and increase the amounts of carbon dioxide, water vapor, and various impurities. This could cause drowsiness or even death. You must remember that space for human living must have air with a good oxygen content and that this air must be kept at a reasonable temperature. It is of utmost importance that fresh air be admitted to provide the oxygen. In the past, this fresh air entered the space by infiltration (leakage) from the outside at door and window openings and through cracks in the structure. However, modern construction is reducing this air leakage. Air-conditioning apparatus, then, must furnish fresh air. Modern units have a controlled fresh-air intake. This fresh air is conditioned and mixed with the recirculated air before it reaches the room. Some conditioned air leaves a building through doors, windows, and other construction joints. Some also leaves by exfiltration. (This means leaking out or being blown out by mechanical means.) Any kind of exhaust fan removes conditioned air. Some of this air is replaced by infiltration on those sides of the building exposed to wind pressure. It is best to bring in replacement fresh air through a makeup air system. When this is done the makeup air can be cleaned. the makeup air can be cooled or heated. a positive pressure can be maintained in the building to keep out airborne dirt, dust, and pollen. (A negative pressure reduces the efficiency of exhaust fans and fuel-fired furnaces.) a definite amount of fresh air is brought into the building for health purposes (oxygen content). Certain areas of a building should have a slightly less positive pressure (5 to 10 percent) than the rest of the building to reduce the spread of odors. Such areas would include the kitchen, lavatories, and where certain industrial operations produce fumes. The amount of fresh air required depends on the use of the space and the amount of fresh air admitted by infiltration. One basic rule is to provide at least 4 cfm of fresh air per person to provide enough oxygen and to remove carbon dioxide. If six people occupy a 1,000-squarefoot space with a 10-foot ceiling, there is 10,000 6, or 1, 667 cubic feet per hour for each person, or 1,667 60 = 27.7 cfm (.78m3 /min). This meets or exceeds ventilating code requirements. One must remember that the air can be handled either to produce positive pressure (higher than atmospheric pressure) in a building or negative pressure (below atmospheric pressure). A positive pressure eliminates infiltration of air from the outside or from other spaces. Positive pressure is produced by using special air intakes to the blowers. A positive pressure assures that all air entering a building can be filtered and cleaned before reaching the occupied space. Hospitals use positive air pressure and require a 100- percent fresh air intake. Negative pressure increases the infiltration at windows and doors. This air is untreated and may be dirty. If the amount of impurities in the inside air-such as odor, smoke, and bacteria-is great enough to require air cleaning, the remedy may be either more ventilation (using fresh air) or improved air cleaning. Ventilation is usually based on air changes per hour for the conditioned space. If the space is 10,000 cubic feet, for example, three changes per hour would mean 3,000 cubic feet per hour or 50 cmf. Three changes every hour is the minimum for a residence during the heating season. As high as 12 changes an hour (in the above case, 200 cfm) are recommended for cooling. It is a good practice to keep the air blowers running all the time to provide good ventilation to all parts of the building. Variable speed blowers are sometimes used. They provide more air movement when the heating or cooling systems are off. An adequate air supply is the best way to control comfort. Body comfort is controlled by evaporation, convection, radiation, and respiration. You must, therefore, control the temperature of the walls, floors, or ceilings to make sure they are not too warm or too cold (radiation). You must also supply enough air to promote good respiration, evaporation, and convection. If the specified conditions are not known, it is best to design for 2 cubic feet per minute per square foot and/or 12 changes of air per hour. It is also very important to remember that people occupying a closed space give off considerable heat. A sleeping person gives off about 200 Btu/hr; a person doing heavy work gives off up to 2,400 Btu/hr. Another way to determine ventilation requirements is to design for 4 cfm to 6 cfm of fresh air per person and for about 25 cfm to 40 cfm of recirculated air per person. This means the system should handle a total of 29 cfm to 46 cfm per person. (1 cfm = 0.0283 cu m/min.) |
Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing |