INSPECTION OF FIRESIDES Boiler firesides should be inspected for signs of damage to the refractory lining, tubes, protection plates, baffles, seal plates, support plates, and other metal parts. This type of inspection is usually conducted when the boiler is secured for fireside cleaning, but it should be conducted each time the boiler is secured. Refractory Inspection Frequent inspection of refractories, together with early repair of any weak or damaged places, can do a lot to prevent refractory failure and to postpone the need for complete renewal. It is a good maintenance practice to inspect the refractories every time the boiler is opened up. Such inspections should be very detailed if you have reason to think the boiler has been operated under severe service conditions-steaming at high rates, burning low-grade or contaminated fuel, or undergoing rapid fluctuations of temperature. Severe conditions cause rapid deterioration of refractories and, therefore, increase the need for frequent inspections. To make a proper inspection of boiler refractories, you should have considerable knowledge of the causes of refractory deterioration. Also, you should know how to tell the difference between serious damage, which may require a complete renewal of brickwork, and less serious damage, which may be dealt with by patching. Slagging and spalling are two of the main causes of refractory deterioration. Slag is formed when ash and other unburnable materials react with the brickwork. Although the ash content of fuel oil is low, there is always enough present to damage the refractories. The most damaging slagforming materials are vanadium salts and sodium chloride. If the slag that forms on the brickwork would remain in place, it would not cause any particular trouble; however, the slag does not remain in place. Instead, it peels off or melts and runs off, taking some refractory with it and exposing a fresh layer of refractory to further slag attack. When deterioration of the brickwork has progressed until only a 3-inch thickness of firebrick remains, the wall should be replaced. When sufficient slag has accumulated on the deck to cause striking with resultant deposits of carbon, the slag should be removed. If less than 1 1/2 inches of firebrick remain after the slag is removed, the entire deck must be replaced. Another type of slag that results from using fuel oil that is contaminated is usually more damaging than peeling slag. This type of slag is very glassy in appearance, and when this slag melts, it usually covers the entire wall or deck. Firebrick shrinkage is another cause of furnace deterioration. True shrinkage (permanent shrinkage) is quite rare in firebrick approved for naval use. However, this defect can occur even in approved firebrick. In any case, it is important to recognize the appearance of true firebrick shrinkage because of the extremely dangerous condition it could create if it should occur. When the firebrick shrinks, the hot-face dimensions of each brick become measurably smaller than the cold-face dimensions. This condition leaves an open space around each brick, and the entire wall or floor becomes loose. A wall or floor having this appearance is DANGEROUS and should be completely renewed as soon as possible. Also, during your inspection, look for signs of unequal stresses that are caused by rapid raising of the furnace temperature while raising steam too rapidly. Emergencies may arise that require the rapid raising or lowering of furnace temperatures, but it is important to remember that the refractories cannot stand this treatment often. As a rule, you will find that raising the furnace temperature too rapidly causes the firebrick to break at the anchor bolts, and lowering the temperature too rapidly causes deep fractures in the firebrick. Also, look for signs of mechanical strain caused by poor operation of the boiler. Continued panting or vibration of the boiler can cause a weakened section of the wall to be dislocated so that the bricks fall out onto the furnace floor. Improper oil-air ratio is the most common cause of boiler panting and vibration. Proper operation of the boiler, with particular attention to the correct use of the burners and forced draft blowers, generally prevents panting and vibration of the boiler. Inspection should also be made of the lower side of the floor pan. Any overheating indicates a loss of insulation and excessive heat penetration. Under normal conditions, the brickwork in a boiler should last for a number of years without complete renewal. Expansion joints should be inspected often for signs of incomplete closure. It is important to keep the joints free of grog, mortar, and refractory particles so that the joints can close properly when the boiler is fired. You can tell if an expansion joint is closing completely when it is heated by inspecting it when it is cold. If the inside of the expansion joint is light in color when the furnace is cold, the expansion joint is closing properly. If an expansion joint does not close properly when heated, the inside is dark and discolored. The same method can be used to tell if cracks in refractory materials are closing properly when the furnace is fired. If the cracks are dark, showing that they do not close, they should be repaired. Since the first firing of a plastic or castable burner front does more damage than any other single firing, the first inspection after installation is a very important one. The unfired burner front may appear to be in perfect condition while actually containing defects of material or workmanship that will show up immediately in the first firing. After the boiler has steamed for several hours, slabs of plastic about 1/2- to 1-inch thick may separate from the burner's front surface and fall off. This is because the surface layer is more densely rammed during installation than the remainder of the material. Radial cracks in the burner fronts may be found on the first inspection. These cracks are not harmful. They are caused by stresses resulting from the normal expansion and contraction of the refractory as it is heated and cooled. After the radial cracks occur, the stresses are relieved and there should be no further cracking of this type. The cracks that eventually result in extensive damage run approximately parallel to the surface of the burner front, and they are called parallel cracks. Parallel cracks usually appear at or slightly behind the leading edge of the bladed cone. They are not dangerous until they actually loosen pieces of the burner front. Improper installation and boiler operation are usually the cause of parallel cracking. A slanting crack in the narrow section between the burners sometimes joins a radial crack. When this occurs, pieces of plastic tend to break off. This type of damage can usually be repaired by a plastic patch. If during your inspection you find that a castable burner front is breaking up after very little service, it is likely that too much water was used in mixing the material during installation. Sometimes the material is already partially set before installation; a common cause of this trouble is that the castable material, while in storage, reacted with moisture in the air and started to set. When castable material sets before it is used, it can never reach full strength. Castable material is also subject to spalling after several hours of service. The peeling material, usually in 1/8-inch strips, should not be removed unless it is in the burner cone and is interfering with combustion. If a castable front is chalky or crumbly, find out how deep the condition goes. If no more than the surface can be rubbed off, the burner front is not seriously damaged. Do not remove the crumbly material. The condition is serious only if the burner cone is affected or if the casing shows signs of overheating. Burner tile should be inspected for loose segments and broken pieces that might cause improper cone angles. The broken or damaged segments can be repaired by patching with plastic fireclay refractory. In some cases a new segment of tile can be installed. When you inspect boiler refractories, it is a good idea to keep in mind the possibility that damage may occur because of operational problems. Although boilers must occasionally be operated under very severe and damaging conditions, a lot of damage to refractories (and, in fact, to other boiler parts as well) is caused by poor operating procedures that are really not necessary under the circumstances. It may be helpful to show operating personnel any refractory damage that appears to be directly related to poor operation of the boiler.
|
Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing |